The model TCSTX is designed for on-line monitoring of water treatment applications and aggressive process chemicals. This 4-Key menu driven transmitter with local display is ideally suited for applications
where 4 – 20mA signals are required and reliable instrumentation is critical. Key features include the menu driven field selectable measuring ranges, large dual segment high content display, adjustable temperature compensation (% deg C), isolated output and reversible cell drive. A NEMA 4X (IP66) enclosure provides excellent durability. A variety of mounting choices are available for wall, panel, pipe or rail installation. Pair the TCSTX with a TCS-3020 toroidal sensor for trouble-free service. TCS-3020 sensors are offered in Noryl construction and can be mounted in a custom CPVC flow cell (p/n: FC95C) for in-line use.
- 4 – 20mA Isolated Output, Loop Powered 16 – 35VDC
- Large Dual Segmented High Content Display Indicates
- Conductivity & Process Temperature Simultaneously
- User-adjustable Temperature Compensation (0 – 4% / deg C)
- 4-Key Menu Driven, Field Selectable Ranges
- Adjustable Zero and Span
- Nema 4X Enclosure with Multiple Mounting Configurations
Specifications:
1) Full Scale Range
0-2,000 uS / 2.000 mS / 20.00 mS / 200.0 mS / 2000 mS - User selectable
2) Sensitivity
0.05% of span or 0.1uS, whichever is greater
3) Repeatability
0.3% of span, or 0.1uS, whichever is greater
4) Non-linearity
0.3% of span or 0.1uS, whichever is greater
5) Zero Drift
<1% span per month, non-cumulative
6) Operating Conditions
-20 to 60deg C (-4 to 140 deg F) , 0-95% R.H. non-condensing conditions
7) Storage Conditions
-30 to 70deg C(-22 to 158 deg F), , 0-95% R.H. non-condensing conditions
8) Location
Designed for hazardous and non-hazardous areas
9) EMI/RFI Influence
Designed to EN 61326-1
10) Temperature Drift
Span or zero, 0.03% of range/degC
11) Stability
0.1% of span per 24 hours
12) Power Requirement
16-35V DC (2-wire device)
13) Warm-up Time
7 seconds to rated performance
14) Response time
6 seconds to 90% step input at lowest setting
15) Output Isolation
600 V galvanic isolation
16) Filter
Adjustable, 0-9.9 minutes additional dampening to 90% step input
17) Enclosure
NEMA 4X (IP66) polycarbonate, wall, pipe or DIN Rail mount. Weatherproof and corrosion resistant.
18) Dimensions
4.4" (112mm) H x 4.4'" (112mm) W x 3.5" (89mm) D.
19) Display
Large, high-contrast, Super-Twist(STN) LCD 4-digit main display with sign, 0.75" (19.1mm) seven-segment characters, 12-digit alpha-numeric second line display, 0.3" (7.6mm) 5 x 7 dot matrix characters
20) Keypad
4-key membrane type with tactile feedback, polycarbonate with UV coating, integral EMI/RFI static shield conductively coated window.
21) Weight
1lb (0.45Kg)
22) Conduit Openings
2 each PG-9. Cord grips included.
23) Temperature Input
Selectable Pt100RTD or Pt1000RTD. ATC is user selectable 0-4%/Deg C
24) Maximum Cable Length
200ft. (61.0m)
Documentation: